Model: DOUBLE PRESS FILTER
Specifications:
Traditional CEF filters have a pump assembly consisting of a positive displacement gear pump with gasket seal and explosion-proof electric motor. With this set, the Diesel sucked from the underground tank, represses the fuel to the press that has a cotton linter filtering element with a retention power of 5 microns, deposited in the reservoir with anti-corrosion protection, where an explosion-proof electrofloat monitors the level of the reservoir .
The press box has a pressure relief valve and manometer to monitor the filtration with total safety. The electrical system is approved according to INMETRO 179.
The pipes are suitable for the flow rates and have a valve that even allows for by-pass operation.
NOTE: The inlet pipes of the filters must be:
CEF 4000 – Ø 1 ½”
CEF 6000 – Ø 2″
CEF 9000 – Ø 2 ½”
CEF 14000 – duas tubulação de 2″
Or for the designer to measure the distance and diameter of the pipe, we inform you that the NPSH req. (Net Positive Suction Head) is 3.5m.
CEF 4000
Usage: | Service Stations |
Tank Type: | Underground |
Technical Description: | Vertical press filter. |
Reservoir (in liters): | 900 |
Filter flow rate (in liters/hour): | 4,300 |
Pump Flow: | 4,500 |
Engine (CV): | 1 |
NOTE: Explosion-proof 1 HP engine. Suitable for 2 (two) pumping units. Without pre-filter, sight hose and sight glass. Return by gravity. | |
Number of Outputs: | 2 |
Pump Type: | Helical gears |
Filter Element: | Cotton linter pulp |
Retention Capacity: | 5 microns |
Number of filter plates: | 24 |
Number of filter papers: | 25 |
Filtering Area: | 0.63 m2 |
Weight: | 470 kg |
Overall dimensions: (L X W X H) | 2250x1700x780 |
Base Dimensions: (L X W) | 2250×780 |
Installation: | Above Tank Level. |
CEF 6000
Usage: | Service Stations |
Tank Type: | Underground |
Technical Description: | Vertical press filter. |
Reservoir (in liters): | 450 |
Filter flow rate (in liters/hour): | 5,500 |
Pump Flow: | 6,000 |
Engine (CV): | 2 |
NOTE: Explosion-proof 2 HP engine. Suitable for 3 (two) pumping units. Without pre-filter, sight hose and sight glass. Return by gravity. | |
Number of Outputs: | 2 |
Pump Type: | Helical gears |
Filter Element: | Cotton linter pulp |
Retention Capacity: | 5 microns |
Number of filter plates: | 30 PLATES 4 HOLES 7 X 7 |
Number of filter papers: | 31 |
Filtering Area: | 1, m2 |
Weight: | 560 kg |
Overall dimensions: (L X W X H) | 2250x1700x780 |
Base Dimensions: (L X W) | 2250×780 |
Installation: | Above Tank Level. |
CEF 9000
Usage: | Service Stations |
Tank Type: | Underground |
Technical Description: | Vertical press filter. |
Reservoir (in liters): | 450 |
Filter flow rate (in liters/hour): | 9000 |
Pump Flow: | 9000 |
Engine (CV): | 3 |
NOTE: WEG 3 HP explosion-proof motor. Suitable for 6) pumping units. Without pre-filter, sight hose and sight glass. Return by gravity. | |
Number of Outputs: | 2 |
Pump Type: | Helical gears |
Filter Element: | Cotton linter pulp |
Retention Capacity: | 5 microns |
Number of filter plates: | 32 PLATES 4 HOLES 7 X 7 |
Number of filter papers: | 33 |
Filtering Area: | 1.15 m2 |
Weight: | 610 kg |
Overall dimensions: (L X W X H) | 2250x1700x780 |
Base Dimensions: (L X W) | 2250×780 |
Installation: | Above Tank Level. |
CEF 14000
Usage: | Service Stations |
Tank Type: | Underground |
Technical Description: | Vertical press filter. |
Reservoir (in liters): | 450 |
Filter flow rate (in liters/hour): | 14000 |
Pump Flow: | 14000 |
Engine (CV): | 4 |
NOTE: Explosion-proof 4 HP engine. Suitable for 7 pumping units. Without pre-filter, sight hose and sight glass. Return by gravity. | |
Number of Outputs: | 2 |
Pump Type: | Helical gears |
Filter Element: | Cotton linter pulp |
Retention Capacity: | 5 microns |
Number of filter plates: | 32 PLATES 4 HOLES 8,5 x 8,5 |
Number of filter papers: | 27 |
Filtering Area: | 2 m2 |
Weight: | 698 kg |
Overall dimensions: (L X W X H) | 2250x1700x780 |
Base Dimensions: (L X W) | 2250×780 |
Installation: | Above Tank Level. |
Other models upon request.